A server’s own hardware, read from its management controller (BMC): fans, temperatures against their own thresholds, power supplies and their redundancy, drives, memory, processors and the event log.

Redfish is the HTTPS interface the DMTF standardised for management controllers, and every current one speaks it: Supermicro, Dell iDRAC, HPE iLO, Lenovo XClarity Controller, ASRock Rack, OpenBMC. It is the right way to watch server hardware. A BMC’s SNMP agent, by contrast, usually describes the BMC itself — its small ARM Linux, its memory, its network links — and not the server it manages (see SNMP).

From the DumbMonit server (or its relay agent) to the device:

PortProtocolPurpose
443TCPRedfish API (HTTPS, default)

All metrics are prefixed dumbmonit_redfish_. Health series are 0 (OK), 1 (Warning) or 2 (Critical), straight from Status.Health.

FamilyMetricsLabels
Serviceinfo (value 1)vendor, product, redfish_version
Systemsystem_health (the system’s own), system_health_rollup (everything it contains), system_power_on, memory_health, processor_health (the controller’s summaries, one value for all DIMMs and all CPUs), memory_total_bytessystem
Chassischassis_health, chassis_health_rollupchassis
Temperaturestemperature_celsius, temperature_upper_critical_celsius and temperature_upper_caution_celsius (the sensor’s own critical and caution thresholds, when it declares them), temperature_healthchassis, sensor
Fansfan_speed_rpm (or fan_speed_percent when the controller reports a percentage), fan_lower_critical_rpm (or _percent: the fan’s own declared minimum, older schema only), fan_health, fan_redundancy_healthchassis, fan / group
Powerpsu_health, psu_output_watts, psu_capacity_watts, power_redundancy_health, power_consumed_wattschassis, psu / group
Voltagesvoltage_volts, voltage_healthchassis, sensor
Storagestorage_health, drive_health, drive_failure_predicted, drive_life_left_percent (SSDs), drive_capacity_bytessystem, storage, drive, media
Controllermanager_health, manager_info (value 1)manager, firmware, model
Logslog_entries, log_critical_entries, log_warning_entriesowner (system or controller), log
Collectionscrape_errors, scrape_duration_seconds

An empty slot is not a failure. A component whose Status.State is Absent (an empty power supply bay, a free DIMM slot, a missing second CPU) or Disabled (a redundancy group that is not configured) produces no series at all. A server delivered with one power supply out of two is healthy, and reads as such.

Two generations of the schema, one set of series. Most controllers in service still publish the older Chassis/{id}/Thermal and Chassis/{id}/Power resources, one request each for every sensor; the newest ones only publish ThermalSubsystem, PowerSubsystem, EnvironmentMetrics and Sensors, one resource per fan, power supply and sensor. DumbMonit reads the older form when it exists and the newer one otherwise; both produce exactly the same series and labels, so a rule written once works on both.

The logs are counted, never read. Log entries can name hosts, addresses and users: DumbMonit keeps only how many entries there are, and how many of the first page the controller serves are Critical or Warning.

The built-in rules that apply: Server fan failed, Server temperature above critical, Power supply redundancy lost, Power supply failed, Drive failure predicted, Server health critical, plus Monitor unreachable.

A Redfish monitor gets its own panel on its page, above the charts, read from what the last probe stored: opening the page never queries the controller. It answers, in this order:

  1. Is the server healthy. One word — Healthy, Degraded or Critical — from the controller’s own health and roll-ups, and under it every component that pulls it down, in a sentence: CPU1 Temp is at 47 °C, at or above its critical threshold of 45 °C, Power supply redundancy is lost, Drive 3 predicts its own failure. When the controller rolls the server up as degraded without naming anything DumbMonit reads, the panel says so and points to its event log. Below: power state, power draw, installed memory and the controller’s firmware.
  2. Are fans and temperatures inside their limits. Each sensor is compared with the thresholds the controller declares for that sensor — its caution and critical temperatures, a fan’s minimum speed — never with a number of DumbMonit’s. A sensor that declares no threshold shows its reading and no verdict, unless the controller itself reports it degraded. Problems are listed first.
  3. Is power redundant. Each redundancy group (Redundant, Redundancy degraded, Redundancy lost), then each power supply present with its output against its capacity and its state. With no redundancy group, the panel says the controller declares none: a single supply, or redundancy not configured.
  4. Are the drives healthy. Each storage controller, then each drive with its capacity, the life left of an SSD and its state; Failure predicted comes before anything else.
  5. Memory, processors and controller: the controller’s one-word summaries for all DIMMs and all CPUs, the management controller’s own health, model and firmware, and the voltages.
  6. Event logs: entries counted by severity. Entries stay until someone clears the log, so a critical count can be old news: it is shown, but it does not change the server’s health word.

Empty bays and free slots never appear: they produce no series. Every state is a word as well as a colour, and an unknown value reads ”—”, never 0.

Create a read-only account on the management controller

Section titled “Create a read-only account on the management controller”
  1. Open the web interface of the management controller (BMC), not the operating system of the server.

  2. Create a local user named as follows, with a long password used nowhere else.

    dumbmonit
  3. Give it the read-only right of your vendor, listed below.

  4. In DumbMonit, enter the controller address (bmc.lan or 10.0.0.50) with that user name and password.

  • Supermicro: privilege User, account type Redfish — Configuration → Users → Add User
  • Dell iDRAC: role Read Only — iDRAC Settings → Users → Local Users → Add
  • HPE iLO: Login privilege only — Administration → User Administration → New; untick the others
  • Lenovo XClarity Controller: role Read-only — BMC Configuration → User/LDAP → Create
  • ASRock Rack: privilege User — Settings → User Management

Vendor documentation: https://www.dmtf.org/standards/redfish

The menu names are those of current firmware; older generations move them around but keep the same roles. On Supermicro, the account type shown when creating a user decides which interfaces it may use: an account without Redfish access is refused with a 401 even with the right password.

DumbMonit only reads: fans, temperatures, voltages, power supplies, drives, memory and processor summaries, and how many log entries there are by severity. It never powers the server on or off, never changes a setting and never reads the text of the logs. A controller answers slowly and a full read takes several requests: if the device reports timeouts, raise DUMBMONIT_PROBE_TIMEOUT_SECS on the server.

To check from any machine on the management network that the account can read Redfish (the command asks for the password and prints the server’s name and health):

curl -k -u dumbmonit https://bmc.lan/redfish/v1/Systems

The menu names above are those of current firmware; older generations move them around but keep the same roles. On Supermicro, the account type shown when creating a user decides which interfaces it may use: an account without Redfish access is refused with a 401 even with the right password.

CredentialFields
Management controller accountUser name and password of the read-only account.

Address: the controller’s host name or IP, for example bmc.lan or 10.0.0.50. The default port is 443; write host:port for another one, or a full URL (https://bmc.lan:8443).

OptionDefaultEffect
port443HTTPS port, if the address does not give one.
insecure_tlsfalseAccept a self-signed certificate.
request_timeout_seconds8Time allowed for each Redfish call, from 1 to 120.
authbasicbasic sends the user name and password with every request and leaves nothing open on the controller. session logs in once and reuses the session token (X-Auth-Token), reopening it only when the controller refuses it and closing the one it replaces. Use it only if the controller refuses basic authentication: controllers have only a handful of session slots.
storagetrueRead the storage controllers and every drive behind them. One request per drive.
logstrueCount the entries of the system event log and of the controller’s own log, by severity.

A full read is a few dozen requests: the service root, then each system, chassis and controller, their thermal and power resources, the storage controllers and drives, the log services. DumbMonit sends at most four at a time. A slow controller may need a longer probe timeout (DUMBMONIT_PROBE_TIMEOUT_SECS, see Configuration) and a probe interval of two minutes or more.

SymptomLikely cause
Authentication refusedWrong password, or the account is not allowed to use Redfish (Supermicro account type, iLO “Login” privilege missing).
Insufficient privilegesThe role is too low for one resource; the rest of the read still goes through. Some controllers hide the event log from their lowest role.
TLS certificate rejectedThe controller’s self-signed certificate: tick “Accept an unverifiable certificate”, or install a trusted certificate on the controller.
Timed outThe controller is slow to answer: raise DUMBMONIT_PROBE_TIMEOUT_SECS, turn off storage or logs, or lengthen the interval.
No temperature thresholdsThe controller does not publish UpperThresholdCritical for that sensor: the temperature is still recorded, but the built-in rule cannot compare it to anything.